14) Check air temperature differentials across the coil on indoor unit in both heating and cooling modes and record information.
15) Check interconnecting refrigerant pipework.
16) Check pipework insulation replace damaged sections as required.
17) Inspect and clean outdoor heat exchanger (coil).
18) Carry out refrigerant leek test as required by EC842/2006 ('F' gas regulations).
19) Check temperature differentials across the coil on the outdoor unit in both heating and cooling modes, and record information.
20) Record the ambient temperature in the vicinity of the condensing unit.
21) Check the electrical connections on the outdoor unit.
22) Check supply voltages.
23) Check earth loop impedance and record information.
24) Check condensing unit amperage draw in both heating and cooling modes and record
information.
25) Check both high and low running pressures in both heating and cooling modes and
record information
26) Check all covers are secure.
27) Check with the client are they happy with the systems operation.Depending on the environment, the frequency of this service may need to be increased, particularly item 4. Failure to maintain the system to the above minimum recommendations could result in the warranty becoming null and void.